Mini Mock on Power System & Electrical Machines: ESE 2018
Attempt now to get your rank among 252 students!
Question 1
The figure shows a two-generator system supplying a load of PD = 40 MW, connected at bus 2.
The fuel cost of generators G1 and G2 are:
C 1 = 10,000 Rs / MWh and C2 = 12,500 Rs/MWh and the loss in the line is Ploss(pu) = 0.5 , where the loss coefficient is specified in pu on a 100 MVA base. The most economic power generation schedule in MW is
The fuel cost of generators G1 and G2 are:
C 1 = 10,000 Rs / MWh and C2 = 12,500 Rs/MWh and the loss in the line is Ploss(pu) = 0.5 , where the loss coefficient is specified in pu on a 100 MVA base. The most economic power generation schedule in MW is
Question 2
For a power system network with n nodes, Z33 of its bus impedance matrix is j0.5 per unit. The voltage at node 3 is 1.3 ∠–10 ° per unit. If a capacitor having reactance of –j3.5 per unit is now added to the network between node 3 and the reference node, the current drawn by the capacitor per unit is
Question 3
For a two machine system with losses, with the transfer impedance being resistive, the maximum value of the sending end power and the maximum receiving end power will occur at power angles in such a manner that
Question 4
A uniformly distributed load on a distributor of length 500 m is rated at 1 A per metre length. The distributor is fed from one end at 220 V. The voltage drop at a distance of 400 metres from the feeding point is ________ V. (Assume a loop resistance of 2X10-5Ω/m)
Question 5
A two bus system has loss coefficient as
Question 6
When a fault occurs in a power system the following sequence currents are recorded.
Izero = -j1.123 p.u
Ipositive = j1.923 p.u
Inegative = -j0.8 p.u
The fault is
Izero = -j1.123 p.u
Ipositive = j1.923 p.u
Inegative = -j0.8 p.u
The fault is
Question 7
In induction type directional over current relay the driving torque is due to interaction of magnetic fields derived from
Question 8
A 75 NVA, 10 kV synchronous generator has Xd = 0.4 p.u. The Xd value (in p.u.) is a base of 100 MVA, 11 kV is
Question 9
A three phase, wound rotor induction motor is to be operated with slip energy recovery in the constant torque mode, when it delivers an output power P0 at slop s. then theoretically, the maximum power that is available for recovery at the rotor terminals, is equal to
Question 10
Which of the following are the variable losses in a rotating machine?
Question 11
Consider the following statements:
The armature torque in a dc motor is a function of
1) Field flux
2) Armature current
3) Speed
4) Damping
The armature torque in a dc motor is a function of
1) Field flux
2) Armature current
3) Speed
4) Damping
Question 12
Consider the following statements:
As a three-phase induction motor is loaded from no-load to rated load.
1) There is an improvement in the power factor
2) The torque increases almost in proportion to slip
3) The air-gap flux falls sharply
Which of the above statements are correct?
As a three-phase induction motor is loaded from no-load to rated load.
1) There is an improvement in the power factor
2) The torque increases almost in proportion to slip
3) The air-gap flux falls sharply
Which of the above statements are correct?
- 252 attempts
- 1 upvote
- 5 comments